This section contains information about facility characteristics that must be considered for the installation or operation of an hp server. Facility characteristics are:
The computer room floor must be able to support the total weight of the installed hp server as well as the weight of the individual cabinets as they are moved into position. Floor loading is usually not an issue in nonraised floor installations. The information presented in this section is directed toward raised floor installations.
Raised floor loading is a function of the manufacturer's load specification and the positioning of the equipment relative to the raised floor grid. While Hewlett-Packard cannot assume responsibility for determining the suitability of a particular raised floor system, it does provide information and illustrations for the customer or local agencies to determine installation requirements. The following guidelines are recommended:
Table C-2 Floor Loading Term Definitions
The average floor load value is not appropriate for addressing raised floor ratings at the floor grid spacing level. However, it is useful for determining floor loading at the building level, such as the area of solid floor or span of raised floor tiles covered by the hp server footprint. This section contains an example of a computer room raised floor system that is satisfactory for the installation of an hp server. Based on specific information provided by Hewlett-Packard, Tate Access Floors has approved its Series 800 all-steel access floor with bolt-together stringers and 24 in. (61.0 cm) by 24 in. (61.0 cm) floor panels. In the event that the flooring is being replaced or a new floor is being installed, Tate Access Floors recommends its Series 1250 all-steel access floor with bolt-together stringers and 24 in. (61.0 cm) by 24 in. (61.0 cm) floor panels be used to support the hp installation.
The following table lists specifications for the Tate Access Floors Series 800 raised floor system. Table C-3 Typical Raised Floor Specifications
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|||||||||||||||