This section contains information about facility characteristics that must be considered for the installation or operation of an hp server. Facility characteristics are:

  • Floor loading

  • Windows

  • Altitude effects

Floor Loading

The computer room floor must be able to support the total weight of the installed hp server as well as the weight of the individual cabinets as they are moved into position.

Floor loading is usually not an issue in nonraised floor installations. The information presented in this section is directed toward raised floor installations.

NOTE: An appropriate floor system consultant should verify any floor system under consideration for an hp server installation.

Raised Floor Loading

Raised floor loading is a function of the manufacturer's load specification and the positioning of the equipment relative to the raised floor grid. While Hewlett-Packard cannot assume responsibility for determining the suitability of a particular raised floor system, it does provide information and illustrations for the customer or local agencies to determine installation requirements.

The following guidelines are recommended:

  • Because many raised floor systems do not have grid stringers between floor stands, the lateral support for the floor stands depends on adjacent panels being in place. To avoid compromising this type of floor system while gaining under floor access, remove only one floor panel at a time.

  • Larger floor grids (bigger panels) are generally rated for lighter loads.

CAUTION: Do not position or install any equipment cabinets on the raised floor system until you have carefully examined it to verify that it is adequate to support the appropriate installation.

Floor Loading Terms

Table C-2 Floor Loading Term Definitions

TermDefinition
Dead loadThe weight of the raised panel floor system, including the understructure. Expressed in lb/ft2 (kg/m2).
Live loadThe load that the floor system can safely support. Expressed in lb/ft2 (kg/m2).
Concentrated loadThe load that a floor panel can support on a 1-in2 (6.45 cm2) area at the panel's weakest point (typically the center of the panel), without the surface of the panel deflecting more than a predetermined amount.
Ultimate loadThe maximum load (per floor panel) that the floor system can support without failure. Failure expressed by floor panel(s) breaking or bending.Ultimate load is usually stated as load per floor panel.
Rolling loadThe load a floor panel can support (without failure) when a wheel of specified diameter and width is rolled across the panel.
Average floor loadComputed by dividing total equipment weight by the area of its footprint. This value is expressed in lb/ft2 (kg/m2).

 

Average Floor Loading

The average floor load value is not appropriate for addressing raised floor ratings at the floor grid spacing level. However, it is useful for determining floor loading at the building level, such as the area of solid floor or span of raised floor tiles covered by the hp server footprint.

Typical Raised Floor Site

This section contains an example of a computer room raised floor system that is satisfactory for the installation of an hp server.

Based on specific information provided by Hewlett-Packard, Tate Access Floors has approved its Series 800 all-steel access floor with bolt-together stringers and 24 in. (61.0 cm) by 24 in. (61.0 cm) floor panels.

In the event that the flooring is being replaced or a new floor is being installed, Tate Access Floors recommends its Series 1250 all-steel access floor with bolt-together stringers and 24 in. (61.0 cm) by 24 in. (61.0 cm) floor panels be used to support the hp installation.

NOTE: If the specific floor being evaluated or considered is other than a Tate Series 800 floor, the specific floor manufacturer must be contacted to evaluate the floor being used.

The following table lists specifications for the Tate Access Floors Series 800 raised floor system.

Table C-3 Typical Raised Floor Specifications

Item[1]Rating
Dead load7 lb/ft 2 (34.2 kg/m2)
Live load313 lb/ft 2 (1528.3 kg/m2)
Concentrated load[2]1250 lb (567 kg)
Ultimate load4000 lb (1814 kg) per panel
Rolling load400 lb (181 kg)
Average floor load500 lb (227 kg)

[2] With 0.08 in (0.2 cm) of span maximum deflection

 

Windows

Avoid housing computers in a room with windows. Sunlight entering a computer room may cause problems. Magnetic tape storage media is damaged if exposed to direct sunlight. Also, the heat generated by sunlight places an additional load on the cooling system.